Series and Parallel solar arrays
Generally speaking, parallel arrays of nominal 12v panels are used with electrical:solar:charge_controller#pwm charge controllers and serial arrays or higher nominal voltage panels are used with MPPT controllers.
Series
Series arrays are used to generate higher voltages to feed the controller.
- PRO
- higher PV voltage can run in relatively thinner wires to the charge controller
- serial connections can provide some charging in low light situations where lower voltage parallel or single-panel connections might not. Imagine two nominal 12v panels running at 11v at sunrise; the series arrangement might yield ~22v (battery charging) instead of 11v (voltage too low to charge battery). Note that power harvestable at those times may be quite low.
- higher-voltage serial configurations with MPPT controllers may provide more power under partial shading
- higher voltages work well with MPPT controllers
- higher voltages can charge higher voltage battery systems like 24v.
- more efficient than parallel when mixing PV of same Imp but different Vmp[1]
- slightly better than parallel when mixing PV of different Imp and Vmp[2]
- higher voltages can help overcome minimum delta requirements to get the MPPT algo running (Victron controllers, for example, require +5v to start and +1v to maintain MPPT).
- CON
- series arrays can generate quite high operating voltages. Be sure your controller can handle the VoC with edge effect.
- requires MPPT charger to get full use of high-voltage arrays under normal conditions.
- thin film panels are generally not recommended for use in serial arrays
- short serial strings are more susceptible to partial shading losses than parallel
Parallel
- PRO
- less impacted by partial shade[3] when using PWM controllers
- more efficient than series when mixing PV of same Vmp but different Imp[4]
- can use charge controllers with lower max voltage input rating
- can use simpler, less expensive PWM charge controllers with nominal 12v panels without losing much efficiency
- CON
- may not provide sufficient voltage to charge battery during very bad conditions (insolation < 20%)
- may not provide sufficient voltage to charge higher voltage (20 or 24v) battery banks
Series-Parallel
Consider this scenario:
- 4 panels
- 150w
- Vmp == 19v
- Voc == 22.8
- Imp == 7.9A
- MPPT controller with 60v maximum input voltage
A fully-series configuration (1p4s) would have a Voc of 91.2v, greatly exceeding the controller's input spec of 60v, and it's common to want to have 20% voltage headroom above Voc.
A fully-parallel configuration (4p1s) would require 3x 2-into-1 MC4 adapters or 1x 4-into-1 adapter. The wiring from the array would need to carry 30A+ to the controller, necessitating heavier wiring that would cost more and might not even fit the controller terminals. It might be unable to charge at all under extreme low-light conditions.
A compromise might be series-parallel array (2p2s) with 45.6Voc and ~16A. This would require 1x 2-into-1 MC4 adapter to combine the two serial strings. Voltage is low enough for the controller, but high enough to allow low-light charging and the use of lighter wiring.